{"id":78912,"date":"2022-03-23T02:26:43","date_gmt":"2022-03-23T00:26:43","guid":{"rendered":"https:\/\/gahzly.com\/%d8%a3%d9%86%d8%b8%d9%85%d8%a9-%d8%a7%d9%84%d8%aa%d8%a3%d8%b1%d9%8a%d8%b6-%d8%a7%d9%84%d9%83%d9%87%d8%b1%d8%a8%d8%a7%d8%a6%d9%8a%d8%a9\/"},"modified":"2023-10-31T19:05:27","modified_gmt":"2023-10-31T17:05:27","slug":"electrical-grounding-systems","status":"publish","type":"post","link":"https:\/\/gahzly.com\/en\/\u0645\u0642\u0627\u0644\/electrical-grounding-systems\/","title":{"rendered":"Electrical grounding systems 2"},"content":{"rendered":"<header class=\"entry-header \">\n<div class=\"ast-single-post-order\">\n<h2><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">Electrical grounding systems<\/span><\/span><\/h2>\n<\/div>\n<div class=\"post-thumb-img-content post-thumb\"><\/div>\n<\/header>\n<div class=\"entry-content clear\">\n<p><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">Electrical grounding systems are a very wide field that includes the grounding of electric current generators, methods of grounding electrical transformers, grounding electronics to ensure that they are not subject to interference from the main grounding, as well as the relationship of grounding systems with various electrical protection devices. <\/span><span style=\"vertical-align: inherit;\">Despite the breadth of this field, the literature usually presents it by explaining the methods of grounding the different transformers and connecting the grounding point of them to the loads. <\/span><span style=\"vertical-align: inherit;\">The focus is on grounding systems, starting from the second end of the distribution transformer, because before this point from the primary end of the transformer to the electric generators, it is electrically isolated (but magnetically connected) from the secondary end of the distribution transformer, which makes it possible to overlook it to simplify the matter. <\/span><span style=\"vertical-align: inherit;\">Also, the secondary end of the low-voltage distribution transformers is what eventually feeds the loads, which makes the relationship between the grounding of the loads and this transformer a close relationship.<\/span><\/span><\/p>\n<p><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">The field of electrical grounding systems is usually introduced by\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">IEC 60364<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> \u00a0and\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">IEEE 80\/81 standards<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> \u00a0and the resulting literature in the field. <\/span><span style=\"vertical-align: inherit;\">Therefore, this article will start from the same base and give a brief introduction in this field through these two standards (without going too deep into\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">IEEE<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> standards) with multiple additions, the most important of which is the \u00a0famous <\/span><span style=\"vertical-align: inherit;\">Schneider\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">Electrical Installation Guide .<\/span><\/span><\/span><\/p>\n<p><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">The purpose of electrical grounding systems can be summarized in two main points:<\/span><\/span><\/p>\n<p><strong><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">A- Ground Protection:-<\/span><\/span><\/strong><\/p>\n<p><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">Connecting current-conducting surfaces, grounding points of sockets, etc. to earth protects us from exposure to electric\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">shock<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> \u00a0by making sure that the voltage of the conductive surfaces is kept equal to the earth&#8217;s voltage. <\/span><span style=\"vertical-align: inherit;\">After the failure of the electrical insulation of any of the wires and their contact with any metal surface, the current will pass directly to the ground instead of passing through the body of any person touching that surface, or passing through any flammable material and causing a fire, or passing through devices that are not intended for such a high current. causing damage to it.<\/span><\/span><\/p>\n<p><strong><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">B- Functional grounding:-<\/span><\/span><\/strong><\/p>\n<p><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">What is meant by functional grounding is the current-carrying grounding line returning to the current source, as is practiced in some of the grounding systems presented in this article. <\/span><span style=\"vertical-align: inherit;\">One of the power transmission systems based on the return of current through the ground is the\u00a0 <\/span><\/span><a href=\"https:\/\/en.wikipedia.org\/wiki\/Single-wire_earth_return\" target=\"_blank\" rel=\"noopener\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">Single-Wire Earth Return system<\/span><\/span><\/a><\/p>\n<h2><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">A &#8211;\u00a0 <\/span><\/span><strong><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">Basic requirements for grounding electrical systems:<\/span><\/span><\/strong><\/span><\/h2>\n<p><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">The parts of electrical grounding systems are defined as follows:<\/span><\/span><\/p>\n<div class=\"wp-block-image\">\n<figure class=\"aligncenter size-large is-resized\"><figcaption><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">Illustration of the components of the grounding system according to the number shown in the picture:<\/span><\/span><\/figcaption><\/figure>\n<\/div>\n<p><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">1- (No. 1 in the picture above) \u2013 the\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">Earth Electrode<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> \u00a0, which is a single conductor (copper cable without insulation), or a group of conductors connected together and located underground (under the soil) with the possibility of\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">Rode<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> rods \u00a0planted in the ground and connected with the conductors To form a grounding network under the soil. <\/span><span style=\"vertical-align: inherit;\">And the rods are planted in the ground at sufficient distances so that the maximum value of the current passing through one of them does not affect or raise the voltage of the rest. <\/span><span style=\"vertical-align: inherit;\">The following picture provides a more detailed illustration of the shape of the grounding grid placed under the soil.<\/span><\/span><\/p>\n<div class=\"wp-block-image\">\n<figure class=\"aligncenter size-large is-resized\"><\/figure>\n<\/div>\n<p><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">2- The Earthing\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">Conductor<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> \u00a0is a conductor (cable), or group of conductors, that connects the main grounding line (No. 6 in the image above) to the\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">Earth Electrodes<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> \u00a0(No. 1). <\/span><span style=\"vertical-align: inherit;\">Its practical design looks as shown in the two pictures here:<\/span><\/span><\/p>\n<div class=\"wp-block-image\">\n<figure class=\"aligncenter size-large is-resized\"><\/figure>\n<\/div>\n<div class=\"wp-block-image\">\n<figure class=\"aligncenter size-large is-resized\"><\/figure>\n<\/div>\n<p><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">3 &#8211;\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">Protective Conductor<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> \u00a0or\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">Protective Earthing (PE)<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> \u00a0responsible for connecting all metal surfaces of electrical devices together in the facility and connecting them to the same main earthing line (No. 6). <\/span><span style=\"vertical-align: inherit;\">An example of this protective conductor is the third line plug\/plug (often the longest and middle to the top) found in homes. <\/span><span style=\"vertical-align: inherit;\">As well as ground lines for air conditioners and other loads connected to the body of the distribution board. <\/span><span style=\"vertical-align: inherit;\">They are usually yellow and green.<\/span><\/span><\/p>\n<p><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">4 \u2013\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">Extraneous Conductive Part Defined<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> \u00a0by the British Standard\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">BS 7671<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> \u00a0as devices that meet the three conditions together:<\/span><\/span><\/p>\n<ul>\n<li><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">1- It must be made of a conductive material<\/span><\/span><\/li>\n<li><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">2- It should be liable to bear the earth\u2019s effort (such as if its surface is in contact with the ground).<\/span><\/span><\/li>\n<li><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">3- It shall not be part of any electrical system<\/span><\/span><\/li>\n<\/ul>\n<p><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">As you can see from the definition, you do not need to ground every metal in your facility or home because the second requirement is that this metal is liable to carry an electric potential. <\/span><span style=\"vertical-align: inherit;\">The reason for this condition is that if any of the live wires come into contact with the surface of any electrical device (such as the surface of a microwave oven, for example), then when a person touches the surface of the microwave on the one hand and the surface of any other metal object that carries the earth&#8217;s voltage on the other hand, the current will pass through his body, which is what should be banned. <\/span><span style=\"vertical-align: inherit;\">From this rule, you can exclude all objects that cannot support the effort of the earth, such as door handles (for wooden doors), window frames, and others. <\/span><span style=\"vertical-align: inherit;\">There is also another obvious condition that is not mentioned in the list above, which is accessibility and touchability of the device. <\/span><span style=\"vertical-align: inherit;\">Therefore, you can exclude pipes buried underground or behind a wall from the list. <\/span><span style=\"vertical-align: inherit;\">Metal surfaces covered with an electrical insulator such as plastic and others are also excluded.<\/span><\/span><\/p>\n<p><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">From the same point of view, and based on the method of installing and connecting the various devices, it is possible to exclude pieces such as stair railings, metal tables, and others. <\/span><span style=\"vertical-align: inherit;\">As a general rule, pieces with electrical resistance must be grounded to earth equal to or greater than the following:<\/span><\/span><\/p>\n<p class=\"has-text-align-center\"><span class=\"ugb-highlight\">R &lt; Vo\/Ib<\/span><\/p>\n<p><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">Where the voltage\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">Vo\u00a0<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> is the voltage of the electrical system in the facility ( <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">230V\u00a0<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> for example) and\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">Ib<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> \u00a0is the limit of current allowed without causing harm to humans ( <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">30mA\u00a0<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> according to\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">IEC<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> standards ). <\/span><span style=\"vertical-align: inherit;\">As an example of\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">230V\u00a0<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> , any piece with a resistance higher than\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">230\/0.030 = 7.66OHM<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> \u00a0between it and the earth must be grounded with a separate cable.<\/span><\/span><\/p>\n<p><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">5 &#8211;\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">Bonding Conductor<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> \u00a0, which aims to connect all metal parts together to ensure that no voltage difference forms between any of them and the ground, and creates what is known as\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">Equipotential Bonding<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> . <\/span><span style=\"vertical-align: inherit;\">It is used to connect the different pieces that were explained in the previous point.<\/span><\/span><\/p>\n<p><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">The linking of all metal pieces together is known as the\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">Equipotential Bonding\u00a0<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> system according to\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">IEC\u00a0<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> standards , and it was established with the aim that if any of the various metal surfaces in the facility (such as water or gas pipes) come into contact with any of the live electrical voltage lines, the voltage on all These surfaces will be equal (because it will become like a single metallic body without any electrical resistance between its parts), so no current discharge will occur anywhere else to save the lives of people and devices until the protection devices catch the error and separate the circuit.<\/span><\/span><\/p>\n<p><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">6 &#8211; The main earthing\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">terminal<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> \u00a0, which is\u00a0 the <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">bar\u00a0<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> or the metal tape to which all the grounding points in the facility are connected from the connection connections (No. 5) and protection conductors (No. 3) as explained in the previous points. <\/span><span style=\"vertical-align: inherit;\">It is usually located inside the\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">Distribution Boards <\/span><\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">\u00a0(as the following picture)\u00a0<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> , or\u00a0 the <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">Switchboard\u00a0<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> , etc., but some local designs and standards require its presence outside the facility or building, as shown in some of the previous pictures. <\/span><span style=\"vertical-align: inherit;\">Also, there may be several bars\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">in\u00a0<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> several different distribution boards, so they are also all connected to each other.<\/span><\/span><\/p>\n<div class=\"wp-block-image\">\n<figure class=\"aligncenter size-large is-resized\"><\/figure>\n<\/div>\n<p><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">7-\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">Removable Link<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> earthing system separation piece \u00a0for testing the resistance and validity of the ground rods.<\/span><\/span><\/p>\n<h2><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">B &#8211; Types of electrical grounding systems:<\/span><\/span><\/h2>\n<p><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">After presenting the methods of connecting the various loads and pieces to the grounding points in the facility, you must know the relationship between those grounding points and the electrical distribution transformer, which will be explained in this part of the article.<\/span><\/span><\/p>\n<p><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">There are different types of grounding systems and the choice of any of them determines the type or protection requirements for the electrical system and how it is connected to the loads. <\/span><span style=\"vertical-align: inherit;\">These different types fall under three main types that are different from each other, and the network designer chooses any of them during his design of the electrical distribution system according to his needs and in accordance with the standards and requirements followed in his country. <\/span><span style=\"vertical-align: inherit;\">Choosing the type of grounding system by the network designer will result in three important and independent decisions:<\/span><\/span><\/p>\n<ul>\n<li><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">The method of connecting the neutral line in the network and its relationship to the apparent parts and pieces of the loads.<\/span><\/span><\/li>\n<li><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">Use a\u00a0 separate <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">Protective Earthing (PE)<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> line\/cable or combine \u00a0it with the neutral line and use only one cable.<\/span><\/span><\/li>\n<li><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">How to use ground fault protection devices (from a short circuit with earth or current leakage to earth) to separate the circuit or give an alarm of a ground fault.<\/span><\/span><\/li>\n<\/ul>\n<p><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">The different earthing systems are also known as \u201cEarthing\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">System Arrangements<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> \u201d and describe the method of earthing the lower part of the network on the secondary end of the\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">MV\/LV Transformers<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> \u00a0(specifically the neutral connection\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">of\u00a0<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> the transformer) and how to earth the visible parts of the electrical connections connected to the network. <\/span><span style=\"vertical-align: inherit;\">Grounding methods also describe whether the transformer&#8217;s neutral\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">(N)<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> \u00a0and protective conductor\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">(PE)\u00a0<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> are separate or connected together. <\/span><span style=\"vertical-align: inherit;\">Finally, choose whether the use of a protective device for the increase in current is sufficient, or is there a need for a special protection to read and disconnect the circuit when the insulation of the conductors fails and there is a leakage current to the ground. <\/span><span style=\"vertical-align: inherit;\">All these points have been combined together and covered by the standard as described throughout this article.<\/span><\/span><\/p>\n<p><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">The\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">IEC 60364<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> standard \u00a0classifies the different grounding systems with two letters, the first letter of which identifies the method of connection between the ground and the current-providing equipment (whether it is an electrical transformer, generator, or other), while the second letter identifies the method of connection between the ground or the electrical network and the various electrical equipment (including loads) that are being fed. <\/span><span style=\"vertical-align: inherit;\">The characters available according to the standard are as follows:<\/span><\/span><\/p>\n<ul>\n<li><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">The letter\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">T<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> : symbolizes a direct connection with the ground, which is an abbreviation of the French word\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">Terre\u00a0<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> , which means \u201cland.\u201d<\/span><\/span><\/li>\n<li><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">The letter\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">I<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> : means the absence of any connection with the ground, or the presence of a connection with high resistance, which is an abbreviation of the word\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">isole\u00a0<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> in French and means \u201cisolation\u201d.<\/span><\/span><\/li>\n<li><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">The letter\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">N<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> : It symbolizes the connection of the neutral coming from the transformer, and it is an abbreviation for the French word\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">Neutre\u00a0<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> , which means \u201cneutral.\u201d<\/span><\/span><\/li>\n<\/ul>\n<p><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">The first letter of the earthing system can only be either\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">T<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> \u00a0or\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">I<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> \u00a0, and the second letter can only be\u00a0 <\/span><span style=\"vertical-align: inherit;\">\u00a0either <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">T<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> \u00a0or\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">N. <\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">This just gives us the following combinations:<\/span><\/span><\/p>\n<ul>\n<li><span class=\"ugb-highlight\">TT<\/span><\/li>\n<li><span class=\"ugb-highlight\">IT<\/span><\/li>\n<li><span class=\"ugb-highlight\">TN<\/span><\/li>\n<li><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">IN\u00a0<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> (it is a non-existent form because it is included in\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">IT\u00a0<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> as you will see later)<\/span><\/span><\/li>\n<\/ul>\n<p><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">The standard also allows the presence of sub-letters following the grounding system\u00a0 , <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">TN\u00a0<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> , as follows:<\/span><\/span><\/p>\n<ul>\n<li><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">TN-C<\/span><\/span><\/span><\/li>\n<li><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">TN-S<\/span><\/span><\/span><\/li>\n<li><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">TN-CS<\/span><\/span><\/span><\/li>\n<\/ul>\n<p><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">Where the letter\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">C<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> is \u00a0an abbreviation for the word\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">Combined\u00a0<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> , i.e. combined, and the letter\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">S<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> is \u00a0an abbreviation for the word\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">Separate\u00a0<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> , i.e. separated. <\/span><span style=\"vertical-align: inherit;\">Hence, we present all the installations of grounding systems in one picture, as you can see here:<\/span><\/span><\/p>\n<figure class=\"wp-block-image size-large is-resized\"><figcaption><\/figcaption><\/figure>\n<h2><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">B1 \u2013\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">TT grounding system<\/span><\/span><\/span><\/h2>\n<p><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">We first start by talking about the\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">TT<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> grounding system . As the type of this system indicates, the neutral end of the current-providing side (such as a transformer) is directly connected to the ground,\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">T<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> \u00a0, through an\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">electrode<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> . <\/span><span style=\"vertical-align: inherit;\">Likewise, the grounding point on the side of the load is connected to a different grounding that is directly related to it through another ground rod, and this grounding includes the grounding of the\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">Protective Conductor<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> \u00a0and the\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">Extraneous Conductive Part<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> . <\/span><span style=\"vertical-align: inherit;\">Also, the neutral point coming out of the transformer goes and is connected to the loads by means of a separate cable. <\/span><span style=\"vertical-align: inherit;\">The only connection between the grounding and neutral of a transformer is that the two are connected together at the transformer end only. <\/span><span style=\"vertical-align: inherit;\">Check out the picture of the\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">TT\u00a0<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> system to learn more about it.<\/span><\/span><\/p>\n<div class=\"wp-block-image\">\n<figure class=\"aligncenter size-large is-resized\"><\/figure>\n<\/div>\n<p><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">The method used to protect humans from the ground leakage current in this system is by using a\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">Residual Current Device<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> \u00a0( <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">RCD<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> ), which is usually set (according to the standards for each country) to disconnect the circuit breaker when the amount of ground leakage current exceeds\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">30mA<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> . <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">TT\u00a0<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> earthing systems\u00a0 <\/span><span style=\"vertical-align: inherit;\">separate the grounding line from the neutral allowing the use of four-phase circuit breakers, but it is necessary to ensure good soil between the loads and the transformer because the only path available for the earth-leaked current to return to the transformer is through the soil of the earth. <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">If the loads are earthed at more than one point (as in the picture), RCD\u00a0<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> protection must be provided\u00a0 <\/span><span style=\"vertical-align: inherit;\">at each of these points.<\/span><\/span><\/p>\n<div class=\"wp-block-image\">\n<figure class=\"aligncenter size-large is-resized\"><\/figure>\n<\/div>\n<p><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">The most important characteristics of this system can be summarized as follows:<\/span><\/span><\/p>\n<ul>\n<li><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">It is the easiest in terms of design and installation.<\/span><\/span><\/li>\n<li><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">It does not require permanent monitoring of the grounding state during the network operation, but a periodic examination of the current leakage protection devices must be carried out.<\/span><\/span><\/li>\n<li><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">Protection against leakage current is ensured by the use of\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">RCDs\u00a0<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> , which also reduces the risk of fire.<\/span><\/span><\/li>\n<li><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">Any current leakage to the ground (such as the failure of the cable insulation, which causes it to connect to the ground or to the surrounding metal objects) will result in circuit separation and loss of the current load. <\/span><span style=\"vertical-align: inherit;\">However, this separation will be limited to the load in which the problem occurred, according to the settings and timing of the separation of the\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">RCD\u00a0<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> circuit breakers connected in series.<\/span><\/span><\/li>\n<li><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">Some loads that by their nature produce a leakage current to the ground (such as welding machines) will disconnect the breaker frequently and undesirably during their work, so these loads will need a separate isolation transformer of their own, or that\u00a0 <\/span><span style=\"vertical-align: inherit;\">specialized <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">RCD\u00a0 devices be used for them.<\/span><\/span><\/span><\/li>\n<\/ul>\n<h2><span style=\"vertical-align: inherit;\"><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\">B2 \u2013 TN<\/span><\/span><span style=\"vertical-align: inherit;\"> grounding system\u00a0<\/span><\/span><\/h2>\n<p><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">The TN\u00a0<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> system\u00a0 is <\/span><span style=\"vertical-align: inherit;\">similar\u00a0 to the <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">TT\u00a0<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> system in the grounding point of the current source (transformer or generator) in terms of connecting the neutral point directly to the ground, but it differs in grounding the end of the loads. <\/span><span style=\"vertical-align: inherit;\">In this system, ground poles planted or connected to the soil are not constructed from the load side (except in some exceptions as you will see below), but it is sufficient to use the neutral and\/or ground cable coming from the transformer for various grounding purposes. <\/span><span style=\"vertical-align: inherit;\">This system is divided into three types according to the arrival of the neutral cable from the current source to the loads as follows:<\/span><\/span><\/p>\n<p><span style=\"vertical-align: inherit;\"><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\">TN-S<\/span><\/span><span style=\"vertical-align: inherit;\"> system\u00a0<\/span><\/span><\/p>\n<p><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">In this system, five cables come out of the transformer, of which one cable is used as a neutral point for loads, while the second is used as a protective earthing <\/span><span style=\"vertical-align: inherit;\">\u00a0( <\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\">PE<\/span><\/span><span style=\"vertical-align: inherit;\"> ) <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">cable . <\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">It is one of the most popular and frequently used systems. <\/span><span style=\"vertical-align: inherit;\">This system is mandatory by\u00a0 <\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\">IEC\u00a0<\/span><\/span><span style=\"vertical-align: inherit;\"> standard for circuits with a cable cross-sectional width of less than\u00a0 <\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\">10\u00a0<\/span><\/span><span style=\"vertical-align: inherit;\"> millimeters ( <\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\">mm2<\/span><\/span><span style=\"vertical-align: inherit;\"> ) or when portable devices (eg those connected to sockets) are used. <\/span><span style=\"vertical-align: inherit;\">Underground wire sheathing or metal reinforcement can be used to connect\u00a0 <\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\">PE\u00a0<\/span><\/span><span style=\"vertical-align: inherit;\"> protection line and is generally applicable.<\/span><\/span><\/p>\n<p><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">An example of using this system in electrical sockets is that one of the two cables is connected to the ground (\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">PE\u00a0<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> ) and the other to the point of the cold line,\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">N<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> , \u00a0as in the picture:<\/span><\/span><\/p>\n<div class=\"wp-block-image\">\n<figure class=\"aligncenter size-large is-resized\"><\/figure>\n<\/div>\n<div class=\"wp-block-image\">\n<figure class=\"aligncenter size-large is-resized\"><\/figure>\n<\/div>\n<p><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">This system saves the costs of establishing an earthing network for each load or facility separately, but it requires an additional grounding cable from the transformer (through the distribution substation) to the loads.<\/span><\/span><\/p>\n<p><span style=\"vertical-align: inherit;\"><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\">TN-C<\/span><\/span><span style=\"vertical-align: inherit;\"> system\u00a0<\/span><\/span><\/p>\n<p><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">It is completely similar to the previous system, except that instead of using two separate cables for neutral and ground, only one cable is used for the two purposes together, as in the picture below, and this cable is called the\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">Protective Earth and Neutral (PEN)<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> cable . <\/span><span style=\"vertical-align: inherit;\">The disadvantage of this system is that if there is a need to open the current circuit breakers for the loads, the circuit breaker will separate the neutral and ground lines together (in order to ensure positive isolation of the\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">load<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> \u00a0), and this is not safe because the grounding point will lose the purpose of its existence. <\/span><span style=\"vertical-align: inherit;\">Also, separating the hot lines only without separating the neutral line is not recommended because it is not a positive separation, in the sense that it will not separate all the lines or cables through which the short current may pass.<\/span><\/span><\/p>\n<p><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">The standard does not prevent a separate grounding point\/bars from being provided at the end of the load and connected to the grounding line coming from the current source, and this also applies to the\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">TN-S<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> system \u00a0as well. <\/span><span style=\"vertical-align: inherit;\">Also, it is forbidden to use the\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">TN-C<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> system \u00a0with a neutral and earth conductor with a cross section of less than\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">10\u00a0<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> square millimeters ( <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">mm2<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> ) and it is forbidden to use it with portable devices (such as those connected to sockets).<\/span><\/span><\/p>\n<p><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">When using this system, care must be taken to have an environment with equal voltage\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">in\u00a0<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> the network, and that is done by planting earthing rods distributed at equal distances as much as possible, because the\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">PEN\u00a0<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> line will carry the neutral current and the\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">3rd Harmonic<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> currents . <\/span><span style=\"vertical-align: inherit;\">Therefore it is necessary to connect the\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">PEN\u00a0<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> line with grounding.<\/span><\/span><\/p>\n<div class=\"wp-block-image\">\n<figure class=\"aligncenter size-large is-resized\"><\/figure>\n<\/div>\n<p><span style=\"vertical-align: inherit;\"><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\">TN-CS<\/span><\/span><span style=\"vertical-align: inherit;\"> system\u00a0<\/span><\/span><\/p>\n<p><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">Here we combine the two previous systems together, as only one cable comes out of the transformer, collecting the ground and neutral, and then it is divided in one of the distribution panels into two separate cables, as in the picture.<\/span><\/span><\/p>\n<div class=\"wp-block-image\">\n<figure class=\"aligncenter size-large is-resized\"><\/figure>\n<\/div>\n<p><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">In this system, it is forbidden to use the\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">PE\u00a0<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> ground line as a neutral point\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">N<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> \u00a0to feed the load after the point of separation of the neutral cable from the ground as shown in the picture below. <\/span><span style=\"vertical-align: inherit;\">It is also forbidden to connect the ground and neutral lines together after their separation, because any unintended separation of the neutral cable at the top of the circuit, then it will result in the separation of the\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">PE<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> ground protection line \u00a0at the bottom of the circuit, which is dangerous and unacceptable.<\/span><\/span><\/p>\n<div class=\"wp-block-image\">\n<figure class=\"aligncenter size-large is-resized\"><\/figure>\n<\/div>\n<p><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">Below you can see how the breaker disconnects current in both\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">TN-C<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> \u00a0and\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">TN-S<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> systems . <\/span><span style=\"vertical-align: inherit;\">In the\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">TN-C<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> system \u00a0, the current will not be separated from the neutral point of the load, because this point itself connects the ground protection line of\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">PE\u00a0<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> loads and should not be cut off under any circumstances, while this can be done in the\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">TN-S<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> system \u00a0because the neutral line is separated from the ground line.<\/span><\/span><\/p>\n<p><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">Although Schneider&#8217;s\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">Electrical Installation Guide<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> specifies \u00a0a way to protect the circuit only by using circuit breakers to increase the current, it is possible to use circuit breakers to protect against leakage current, but after studying each load separately and carefully, and this point will not be discussed in this article.<\/span><\/span><\/p>\n<div class=\"wp-block-image\">\n<figure class=\"aligncenter size-large is-resized\"><\/figure>\n<\/div>\n<p><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">The characteristics of the TN\u00a0<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> earthing system are\u00a0 <\/span><span style=\"vertical-align: inherit;\">summarized as follows:<\/span><\/span><\/p>\n<ul>\n<li><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">The extension of this system in the future after its installation requires caution and study by specialized electricians so as not to confuse the different grounding methods.<\/span><\/span><\/li>\n<li><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">The TN-C<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> earthing system\u00a0 <\/span><span style=\"vertical-align: inherit;\">\u00a0is relatively cheaper than the other two types. It is also forbidden to use it in facilities that have a high risk of fire (such as gas stations) and it is forbidden to use it in systems that have many computers because it will cause harmonics\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">carried\u00a0<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> on the neutral line.<\/span><\/span><\/li>\n<li><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">The\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">TN-S<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> system is characterized by its \u00a0ability to be used with small size conductors. <\/span><span style=\"vertical-align: inherit;\">It is also preferable to use it in networks where there are many computers because it will provide a\u00a0 <\/span><span style=\"vertical-align: inherit;\">clean\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">PE\u00a0 <\/span><\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">ground\u00a0<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> protection line (as opposed to\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">Dirty<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> ), which will prevent any interference or malfunctions in sensitive computers and servers.<\/span><\/span><\/li>\n<\/ul>\n<h2><span style=\"vertical-align: inherit;\"><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\">B3 \u2013 IT<\/span><\/span><span style=\"vertical-align: inherit;\"> grounding system\u00a0<\/span><\/span><\/h2>\n<p><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">The first letter\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">I<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> \u00a0indicates that this earthing system is in which the neutral point of the transformer or generator is not connected to earth, i.e. it is isolated from earth.<\/span><\/span><\/p>\n<p><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">However, this system allows the neutral point to be connected to the ground indirectly through a resistance to the ground, so the neutral grounding system is also called the\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">Impedance-Earthed Neutral<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> resistance .<\/span><\/span><\/p>\n<p><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">As for the load side, the grounding point is connected to the ground, which is indicated by the\u00a0 <\/span><span style=\"vertical-align: inherit;\">letter <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">T.<\/span><\/span><\/span><\/p>\n<p><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">You may wonder why the load is connected to the ground (soil) directly without doing so at the generating end, unless it provides a path for the current to return to its source when any ground fault occurs in the circuit.<\/span><\/span><\/p>\n<p><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">The answer is that the grounding point on the end of the load for systems in which the source is not grounded at all works as a point to ensure equal voltage on the material surfaces of the various electrical devices when any\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">Equipotential Bonding<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> error occurs \u00a0.<\/span><\/span><\/p>\n<div class=\"wp-block-image\">\n<figure class=\"aligncenter size-large is-resized\"><\/figure>\n<\/div>\n<p><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">A resistance can also be connected between the neutral point of the transformer and the ground, as in the following picture.<\/span><\/span><\/p>\n<p><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">The value of this resistance is between\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">1000\u00a0<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> and\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">2000\u00a0<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> ohms.<\/span><\/span><\/p>\n<p><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">IEEE\u00a0<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> standards\u00a0 <\/span><span style=\"vertical-align: inherit;\">classify this resistance into two types, the first is\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">High Impedance Grounding<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> \u00a0and the second is\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">Low Impedance Grounding<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> \u00a0, but this article will not delve further into this distinction between the two systems.<\/span><\/span><\/p>\n<p><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">Here, the grounding point of the loads (which includes all the\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">Extraneous Conductive Part<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> ) is connected to grounding rods.<\/span><\/span><\/p>\n<p><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">The reason for using such a resistance is to adjust the amount of voltage relative to the ground in the current lines, especially when an unacceptable rise occurs in the medium voltage lines coming from the network and others.<\/span><\/span><\/p>\n<div class=\"wp-block-image\">\n<figure class=\"aligncenter size-large is-resized\"><\/figure>\n<\/div>\n<p><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">\u00a0Ungrounded\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">IT<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> systems use\u00a0 a device to monitor the condition of the isolation of the current source&#8217;s neutral (such as a transformer) from ground, known as an <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">Insulation Monitoring Device (IMD)<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> .<\/span><\/span><\/p>\n<p><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">In the event of a fault occurring between one of the power lines and the ground (let&#8217;s call it the first fault), there is no reason to disconnect the circuit, and an alarm can suffice for the maintenance team to investigate and find out the location of the fault.<\/span><\/span><\/p>\n<p><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">However, in the event of another short circuit with earth (the second fault), the circuit must be disconnected to touch the two faulty lines together.<\/span><\/span><\/p>\n<div class=\"wp-block-image\">\n<figure class=\"aligncenter size-large is-resized\"><\/figure>\n<\/div>\n<p><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">The characteristics of this system are summarized as follows:<\/span><\/span><\/p>\n<ul>\n<li><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">This system allows the circuit to continue working and provide current for as long as possible even when the first failure occurs<\/span><\/span><\/li>\n<li><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">Provides an alarm when the first earth fault (or current leakage) occurs in the circuit<\/span><\/span><\/li>\n<li><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">A maintenance team is required to locate the fault while the circuit is working<\/span><\/span><\/li>\n<\/ul>\n<p><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">The following image from\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">IEEE\u00a0<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> shows the type of grounding system used in different countries of the world.<\/span><\/span><\/p>\n<p><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">It should be noted that all systems have their uses.<\/span><\/span><\/p>\n<p><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">It is not black and white and there is no right or wrong answer. <\/span><span style=\"vertical-align: inherit;\">Therefore, the standards classified different grounding systems and left the choice of any of them to engineers around the world.<\/span><\/span><\/p>\n<div class=\"wp-block-image\">\n<figure class=\"aligncenter size-large is-resized\"><\/figure>\n<\/div>\n<p><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">The choice of any of these systems does not depend on which one is safer because they are all equal in terms of human protection if the network is installed properly and in accordance with the conditions of each system.<\/span><\/span><\/p>\n<p><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">Therefore, the choice of any of these systems depends first on the legal requirements in the facility or the country in which the system is installed.<\/span><\/span><\/p>\n<p><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">Secondly, on the priority of continuing the network\u2019s work and the danger of power outages, thirdly on the way and how to operate the network and the presence of individuals for that, and finally on the type of loads connected to the network.<\/span><\/span><\/p>\n<p><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">The network designer can also use the following table from Schneider&#8217;s guide to see the difference between the different systems and determine what is suitable for him.<\/span><\/span><\/p>\n<p><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">Note that system\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">IT\u00a0<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> is mentioned twice in the table, the first time is\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">IT(1)\u00a0<\/span><\/span><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> special in case of the first ground fault in the network and the second time is\u00a0 <\/span><\/span><span class=\"ugb-highlight\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">IT(2)<\/span><\/span><\/span><\/p>\n<p><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">Especially in the event of a second error (in the presence of the first error) in the network.<\/span><\/span><\/p>\n<div class=\"wp-block-image\">\n<figure class=\"aligncenter size-large is-resized\"><\/figure>\n<\/div>\n<p><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">Also, you may need to use more than one grounding system in the same organization or network, according to the type of loads that will be connected to that system.<\/span><\/span><\/p>\n<p><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">In this sense, you can see the most appropriate use in terms of type of load for each of the different grounding systems shown in the table:<\/span><\/span><a href=\"https:\/\/www.gahzly.com\/\"><\/a><\/p>\n<div class=\"wp-block-image\">\n<h4><img loading=\"lazy\" decoding=\"async\" class=\"size-full wp-image-50673 aligncenter\" title=\"Electrical grounding system and its components Electrical grounding system and its components\" src=\"https:\/\/gahzly.com\/wp-content\/uploads\/2021\/12\/editor-1s-188px-15.gif\" alt=\"Electrical grounding system and its components\" width=\"188\" height=\"188\" \/><\/h4>\n<p>gahzly<\/p>\n<h4><span id=\"%D9%8A%D8%B3%D8%B9%D8%AF%D9%86%D8%A7_%D8%B2%D9%8A%D8%A7%D8%B1%D8%AA%D9%83%D9%85_%D8%B5%D9%81%D8%AD%D8%A7%D8%AA%D9%86%D8%A7_%D8%B9%D9%84%D9%89_%D9%85%D9%88%D8%A7%D9%82%D8%B9_%D8%A7%D9%84%D8%AA%D9%88%D8%A7%D8%B5%D9%84_%D8%A7%D9%84%D8%A7%D8%AC%D8%AA%D9%85%D8%A7%D8%B9%D9%8A_%D8%AD%D9%8A%D8%AB_%D9%86%D9%82%D9%88%D9%85_%D8%A8%D9%86%D8%B4%D8%B1_%D8%B9%D8%B1%D9%88%D8%B6_%D8%AD%D8%B5%D8%B1%D9%8A%D8%A9_%D8%B9%D9%84%D9%89_%D9%85%D9%88%D9%82%D8%B9%D9%86%D8%A7_%D8%A7%D9%84%D8%A7%D9%84%D9%83%D8%AA%D8%B1%D9%88%D9%86%D9%8A\" class=\"ez-toc-section\"><\/span><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">We are pleased to have you visit our pages on social networking sites, where we publish exclusive offers on our website.<\/span><\/span><\/h4>\n<p><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">Our Facebook page\u00a0 <\/span><\/span><a href=\"https:\/\/www.facebook.com\/Gahzlystore\/\" target=\"_blank\" rel=\"noopener\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">here<\/span><\/span><\/a><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> .<\/span><\/span><\/p>\n<p><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">Our Twitter account\u00a0 <\/span><\/span><a href=\"https:\/\/twitter.com\/gahzly1\" target=\"_blank\" rel=\"noopener\"><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\">here<\/span><\/span><\/a><span style=\"vertical-align: inherit;\"><span style=\"vertical-align: inherit;\"> .<\/span><\/span><\/p>\n<\/div>\n<\/div>\n","protected":false},"excerpt":{"rendered":"<p>Electrical grounding systems Electrical grounding systems are a very wide field that includes the grounding of electric current generators, methods of grounding electrical transformers, grounding electronics to ensure that they are not subject to interference from the main grounding, as well as the relationship of grounding systems with various electrical protection devices. Despite the breadth [&hellip;]<\/p>\n","protected":false},"author":3,"featured_media":56494,"comment_status":"open","ping_status":"open","sticky":false,"template":"","format":"standard","meta":{"footnotes":""},"categories":[12407],"tags":[9834,8172,7824,12408,8109],"class_list":["post-78912","post","type-post","status-publish","format-standard","has-post-thumbnail","hentry","category-grounding-systems","tag-electrical-en-3","tag-electrical-en","tag-grounding","tag--en"],"featured_image_src":{"landsacpe":["https:\/\/gahzly.com\/wp-content\/uploads\/2022\/03\/15e_ScaddanINTRO.webp",450,300,false],"list":["https:\/\/gahzly.com\/wp-content\/uploads\/2022\/03\/15e_ScaddanINTRO.webp",450,300,false],"medium":["https:\/\/gahzly.com\/wp-content\/uploads\/2022\/03\/15e_ScaddanINTRO-300x200.webp",300,200,true],"full":["https:\/\/gahzly.com\/wp-content\/uploads\/2022\/03\/15e_ScaddanINTRO.webp",450,300,false]},"jetpack_featured_media_url":"https:\/\/gahzly.com\/wp-content\/uploads\/2022\/03\/15e_ScaddanINTRO.webp","_links":{"self":[{"href":"https:\/\/gahzly.com\/en\/wp-json\/wp\/v2\/posts\/78912","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/gahzly.com\/en\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/gahzly.com\/en\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/gahzly.com\/en\/wp-json\/wp\/v2\/users\/3"}],"replies":[{"embeddable":true,"href":"https:\/\/gahzly.com\/en\/wp-json\/wp\/v2\/comments?post=78912"}],"version-history":[{"count":0,"href":"https:\/\/gahzly.com\/en\/wp-json\/wp\/v2\/posts\/78912\/revisions"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/gahzly.com\/en\/wp-json\/wp\/v2\/media\/56494"}],"wp:attachment":[{"href":"https:\/\/gahzly.com\/en\/wp-json\/wp\/v2\/media?parent=78912"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/gahzly.com\/en\/wp-json\/wp\/v2\/categories?post=78912"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/gahzly.com\/en\/wp-json\/wp\/v2\/tags?post=78912"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}